Industrial Wireless Radio Controls
Please Request latest price
Performance
•
3 miles ( 5 km)
line-of-sight w Omni antenna
• Extended range
up to 20 km •
Operation: 120/240VAC or 12VDC
•
Transmitter input N/O Dry contact
•
Receiver with signal strength indicator
• Relay Output SPDT, 6A
Class 2 pilot duty
•
Heavy Duty NEMA4, IP65 UL Fiber enclosure
• License free 154MHz
Industrial MURS band • Factory configured systems, Ready to
operate
• No setup or programming required
■
Complete
system:
One Transmitter 2 Ch in NEM4 Enclosure
One Receiver with Red and Green Lamps
Two Omni Antennas 931487
Operation: Example
■
If Low Level SW Close: Red light ON, Pump Start.
■
If High Level SW Close: Green
light ON, Pump Stop.
Monitoring:
■
Red light indicates the tank
level is low
■
Green light indicates the tank
level is high
|
DISCLAIMER:
Radio control equipment
in not to be used in life safety.
Radio Installations shall be performed by a certified
professional. |
|
|
Remote
operation for: Pumps, Lighting, Process, Alarms, Monitoring,
Valves.
■
Applications:
Industrial Monitoring, Pump control, Monitor remote sites, Tank
Level,
Lighting control, Remote Mobile system, PLC remote, SCADA, Gates.
Factory process control, Alarms, Generators,
Solar, Wire replacement.
|
■
915422
Supply power |
120/240VAC or 12VDC / 7watt |
Inputs |
N/O Normally Open, digital dry
contact |
Transmitter power |
per FCC Part 15.249,
50mV/m @ 3m |
Transmission |
Digital Encoded
Gaussian_frequency-shift_keying |
Channels |
16 addresses per system GFSK |
Input Wiring |
Din Terminals,
Dry Contact |
Response |
Loop 500 msec
|
Weight |
6.8 lb (3.40kg) each unit |
(*) Dimensions |
12"W
x 10"H x 6"D (300 x 250 x 150 mm) |
Specifications
Digital Receiver
|
Supply power |
120/240VAC or 12VDC / 5watt |
Output |
Relay 8Amp, Class 2 pilot duty |
Frequency |
154MHz
• License free MURS band |
Configuration |
DIP switch factory preset |
Compliance |
FCC CFR part 15.247, 95 sub E |
Wiring |
Screw Terminals |
Antenna Z |
50 Ohm |
Ambient temp |
14°
to 140° F (-10° to 60° C) |
Enclosure |
NEMA4,
IP65
|
(*) Final Component layout and Dimension may
vary
|
Typical wiring application example
|